Self Diagnostic / Self Test
Irvine Lighting offers the SELF DIAGNOSTIC / SELF TEST (SDT) feature on many of its exit and emergency lighting fixtures. This feature is becoming increasingly more important in the world of exit and emergency lighting as architects and building owners become more aware of its tremendous value added functions and safety assuring technology.
The heart of the SDT feature is the on-board IC chip that continuously monitors the entire fixture and reports any malfunctions via a user interface. The user interface identifies the exact nature of the problem allowing the occupant or service personnel to take the proper steps to correct it.
The SELF TESTING feature included in the circuitry tests the fixture every 30 days for 15 minutes and once every 12 months for a full 90 minute discharge test simulating a maximum use power failure. After each test it recharges the battery automatically and returns to normal operating mode. Any problems found during or after the test are reported through the user interface.
Our Emergency and Exit Lighting product lines offer many features including: self powered, multi-voltage, battery back-up, remote and self test capabilities, and are available in multiple languages.
|